INDUSTRIAL BURNERS INSTALLATIONS

INDUSTRIAL BURNERS INSTALLATIONS

INDUSTRIAL BURNERS INSTALLATIONS

INDUSTRIAL BURNERS INSTALLATIONS

Flame Safeguard Systems for Multi Burner Environment: Integrated Scanners

Fireye Logo New

  

 

  • Fully microprocessor-based integrated flame scanners with electronic self-checking
  • Two versions with solid-state detectors: 95UVS4 (295-350 nm) and 95IRS4 (700-1700 nm)
  • For continuous operation on oil, gas and coal power & industrial burners, in power, refinery and petrochem lowNOx applications, including Duct Burners, incinerators
  • High discrimination capabilities in difficult multi-burner and multi-fuel environment
  • FFRT 1 - 6 sec.
  • Internal flame relay with automatically set or manually selected ON/OFF thresholds, 21 choices of modulation frequency, adjustable sensor gain, adjustable flame relay ON/OFF thresholds,  
  • Auto Config capability at Flame ON and Flame OFF conditions with manual override: 
    -  the amplitudes of the target flame are automatically measured and stored
    -  optimum flame relay ON/OFF criteria are set and stored
    -  the appropriate sensor gain is automatically selected
  • Automatic aiming – function AIM
  • Four selectable programmable files (e.g. for different fuels or firing rates) 
  • User Interface Module is password protected: alpha-numeric two-line sixteen-character display with five-pushbutton keypad. These provide a continuous indication of flame signal, flame relay status, scanner status as well as the selected mode of operation. The keypad is used for setup and changing operating parameters
  • In case of possible scanner overheating, long distance to flame or tilting burner the fiber optic assembly is available
  • Supply 24 VDC/ 250mA
  • Outputs: Flame Relay NO, Fault Relay NC, 4–20 mA signal
  • Remote communication capability is available via optional “Fireye Explorer” PC software
  • Quick-disconnect: 12-pin of a screw type (basic scanner models)
  • Temperature rating -40 to +65°C, IP66
  • Explosion-proof version ATEX Ex II G/D
  • Approvals: FM, UL, DIN-DVGW, CE  
  • Designed to meet Safety Integrity Level SIL-3  according to Exida FMEDA Report

Insight II IV Flame Scanner1 


Fireye Logo New

 

 

  • Fully microprocessor-based integrated flame scanners
  • Solid-state detectors: type 95UV UV (295 – 320 nm), type 95IR IR (700 – 1 700 nm), type 95DS utilizes both sensors
  • Continuous operation, elctronic self-checking Fail-Safe
  • High and very high discrimination capabilities - good for difficullt multi-burner applications
  • The S1 Model - offers manual selection and adjustment of three modulation frequencies, sensor gain, flame relay ON/OFF thresholds
  • The expanded S2 Model - allows automatic programming (AutoTune) with manual override capability, 21 choices of flame flicker frequency, four selectable programmable files to store setpoints, remote communication capability via RS MODBUS output
  • Model S2 AutoTune - scanner scans the flame flicker frequency spectrum in flame ON, and flame OFF (background radiation present) conditions and then selects the appropriate sensor gain, bandpass frequency, sensor range for optimum flame ON/OFF discrimination and selects also the optimum Flame Relay ON and OFF thresholds
  • In case of possible scanner overheating, long distance to flame or tilting burner the fiber optic assembly is available
  • Flame Failure Response Time (FFRT): selectable 1 to 6 seconds
  • 8 character LED display and 4 push-button password-protected keypad to enable the user to view operating parameters and select setpoints
  • Supply 24 VDC
  • Outputs: flame relay NO, fault relay NC, analogue 4 – 20 mA
  • Quick-disconnect: 12-pin of a screw type (basic scanner models)
  • Temperature rating -40 to +65°C
  • in Model S2 available optional software for start-up or flame analysis
  • Housing is available in explosion-proof version ATEX Ex d IIC T6
  • Approvals: DIN-DVGW, CE  
  • Designed to meet Safety Integrity Level SIL-3  according to EXIDA Report
  • Low installation cost

insight


Fireye Logo New

  

 

  • Fully microprocessor-based integrated flame scanners with electronic self-checking
  • Two versions with solid-state detectors: 85UVF (295-340 nm) and 85IRF (830-1100 nm)
  • For continuous operation on oil and gas power & industrial burners, in power, refinery and petrochem lowNOx applications, including Duct Burners, incinerators
  • High discrimination capabilities in difficult multi-burner and multi-fuel environment
  • Internal flame relay with automatically set ON/OFF thresholds
  • FFRT 1 - 4 sec.
  • The scanner setup procedure during Learning Mode:
    -  the amplitudes of the target flame are automatically measured and stored
    -  optimum flame relay ON/OFF criteria are set and stored
    -  the appropriate sensor gain is automatically selected
  • Automatic aiming – function AIM
  • Advanced diagnostics: the Advanced Trip Diagnostic function allows detecting the cause of the scanner's termination, Trip Threshold Adjustment allows you to set thresholds for flame quality criteria: Average Amplitude, Power Spectrum Density, Best Fit, Peak-to-Median Ratio. 
  • User Interface Module is password protected: pushbutton keypad and informative LEDs. These provide a continuous indication of flame signal, flame relay status, scanner status as well as the selected mode of operation. The keypad is used for setup and changing operating parameters
  • In case of possible scanner overheating, long distance to flame or tilting burner the fiber optic assembly is available
  • Supply 24 VDC/ 200mA
  • Outputs: Flame Relay NO, Fault Relay NC, 4–20 mA signal
  • Quick-disconnect: 8-pin of a screw type (basic scanner models)
  • Temperature rating -40 to +65°C, IP66
  • Explosion-proof version ATEX Ex II G/D
  • Approvals: FM, UL, DIN-DVGW, CE  
  • Designed to meet Safety Integrity Level SIL-3  according to Exida FMEDA Report

Phoenix Series 2

 


Fireye Logo New

 

 

  • Fully microprocessor-based integrated UV/IR flame scanners
  • Utilizes two solid-state detectors: UV (295 – 320 nm), IR (700 – 1 700 nm)
  • Continuous operation, elctronic self-checking Fail-Safe
  • Very high discrimination capabilities in difficult multi-burner and multi-fuel environment - good for all applications
  • Two scanners in one – two independently adjustable Flame Relays e.g. for two fuels, for pilot/igniter and main burner or for start and normal operating conditions
  • Independent settings on each Flame Relay: selection of sensor  IR, UV or both, 21 choices of modulation frequency, adjustable sensor gain, Flame Failure Response Time (FFRT) 1 to 4 seconds, separate settings of relay ON and OFF thresholds, 4-20mA separate for each relay
  • Universal standard/ATEX enclosure with changeable parts:
    -  programming module with interface and VFD display or infrared transmitter module with status LED's communicating with handheld remote communication tool,
    -  module cover with window for ATEX versions or fixing ring for standard version with modules
  • Automatic aiming – function AIM SCANNER
  • Auto Config capability with Manual Config override allows the learning of flame ON conditions and background OFF conditions with optional separate OFF conditions learning for both Flame Relays independently. 
  • 4 selectable Memory Files for saving the settings of both Flame Relays for different conditions
  • User Interface Module: two-line 16-character alpha-numeric VFD display and 5 push-button password-protected keypads to enable the user to view and change operating parameters and select setpoints
  • In case of possible scanner overheating, long-distance to flame or tilting burner the fiber optic assembly is available
  • Supply 24 VDC
  • Outputs: two independent Flame Relays NO/NC, Fault Relay NO, two independent 4–20 mA signals for each flame relay
  • 2 quick-disconnects: 8-pin and 12-pin of a screw type (basic scanner models)
  • Temperature rating -40 to +65°C
  • FM MODBUS remote communication with Fireye Explorer software is available
  • Explosion-proof version ATEX Ex d IIC T6
  • Approvals: FM, UL, DIN-DVGW, CE  
  • Designed to meet Safety Integrity Level SIL-3  according to EXIDA Report

insight ii

scanner Insight II with display module

insight II transmitter

remote communication tool

insight ii remote

pilot skanera


Fireye Logo New

 

 

  • The simplest integrated flame scanner
  • UV Geiger Muller detection tube
  • Wavelength 210 nm (190 – 270 nm) – Solar blind
  • Continuous operation - self-checking with shutter
  • Applications: clean gas or oil fuels flames
  • Flame Failure Response Time: 1 second
  • Basic discrimination capability
  • Input power 24 VDC
  • Flame relay output NO/NC
  • Fault relay output NO
  • Analogue output 4-20 mA
  • Temperature rating -40 to +65 oC
  • Explosion-proof version ATEX Ex d IIC T6
  • Agency approvals: FM, DIN-DVGW, CE
  • Low installation cost

65UV5-1000E simplicity


Fireye Logo New

 

 

  • Fully microprocessor-based integrated IR flame scanner and flame analysis device
  • Two solid-state IR detectors: one for flame frequency characteristic analysis second for flame temperature measurement
  • The Paragon measures the amplitude of the modulation - "flame flicker" in the targeted flame over the wide frequency  range, analyzes the fit of the measured flame characteristics with the learned one stored in the memory and also measures the average flame temperature within the field of view of the scanner 
  • Continuous operation, electronic self-checking Fail-Safe, fault relay signals the faults detected by the scanner 
  • Very high discrimination capabilities in difficult fossil fuels combustion chamber environments 
  • The temperature measurement helps in combustion optimization 
  • Scanner during the set-up procedure learns the flame frequency/amplitude profile and determines the gain, optimum ON/OFF flame relay thresholds and other parameters necessary for the best flame discrimination 
  • Fast Fourier Transform is used to build the real-time flame characteristics and compare them with stored, the learned ones
  • In case of possible scanner overheating, long distance to flame or tilting burner the fiber optic assembly is available 
  • Flame Failure Response Time (FFRT) 1 to 4 seconds
  • Two sets of 8 LED's and 4 status LED's show flame signal, flame temperature, relay status and scanner status as well as a mode of operation
  • 4 push-button password-protected keypad enables the user to change operating parameters and select setpoints 
  • Supply 24 VDC
  • Outputs: Flame Relay NO/NC, Fault Relay NO, Flame Temperature Relay NO, 4–20 mA signals: one for flame strength one for flame temperature
  • Temperature rating -40 to +65°C or extended temperature version +10 to +85°C
  • FM MODBUS remote communication with Fireye Explorer software is available, Paragon Explorer software allows for the temperature measurement settings
  • Approvals: FM, UL, DIN-DVGW, CE
  • Designed to meet Safety Integrity Level SIL-2