INDUSTRIAL BURNERS INSTALLATIONS

INDUSTRIAL BURNERS INSTALLATIONS

INDUSTRIAL BURNERS INSTALLATIONS

INDUSTRIAL BURNERS INSTALLATIONS

IR Flame Scanner 45RM4-1001

Fireye Logo New

 

 

  • A solid-state lead sulphide IR detector, range 700 – 2 500 nm
  • Continuous operation, electronic self-checking
  • High discrimination capability
  • Application: „dirty fuels” – oil, coal, gas
  • Detects the flame ON and OFF conditions by observing the amount of signal at a specific flame flicker frequency filter
  • 16 position frequency filter selector switch in the range of 30 – 180 Hz, gain adjustment potentiometer and 10 LED flame strength indicator on the back of the scanner
  • Works with amplifiers 25SU3-5166/5168 and 25SU3-2000
  • In case of possible scanner overheating, long distance to flame or tilting burner the fiber optic assembly is available
  • Supply voltage 24 VDC from connected FIREYE amplifier
  • Temperature range: -25 to +65°C
  • Available explosion-proof version ATEX Ex d IIC T6
  • Agency approvals: CSA, FM, CE (with an amplifier)

NOTE: The product has been withdrawn from production. Contact IP&S companyfor the selection of a replacement integrated flame scanner