INDUSTRIAL BURNERS INSTALLATIONS

INDUSTRIAL BURNERS INSTALLATIONS

INDUSTRIAL BURNERS INSTALLATIONS

INDUSTRIAL BURNERS INSTALLATIONS

IR Flame Scanner 45RM4-1001

Fireye Logo New

 

 

  • Solid state lead sulphide IR detector, range 700 – 2 500 nm
  • Continuous operation, electronic self checking
  • High discrimination capability
  • Application: „dirty fuels” – oil, coal, gas
  • Detects the flame ON and OFF conditions by observing the amount of signal at specific flame flicker frequency filter
  • 16 position frequency filter selector switch in range 30 – 180 Hz, gain adjustment potentiometer and 10 LED flame strength indicator on back of scanner
  • Works with amplifiers 25SU3-5166/5168 and 25SU3-2000
  • In case of possible scanner overheating, long distance to flame or tilting burner the fiber optic assembly is available
  • Supply voltage 24 VDC from connected FIREYE amplifier
  • Temperature range: -25 to +65°C
  • Available explosion proof version ATEX Ex d IIC T6
  • Agency approvals: CSA, FM, CE with amplifier

NOTE: The product has been withdrawn from production. Contact company IP&S for the selection of a replacement integrated flame scanner

45rm4


By staying on the site you accept the privacy policy. Cookies make it easier for us to provide you with our services. With the usage of our services you permit us to use cookies.
More information Accept Decline