Single Burner Flame Scanners and Controls
- Ionisation (rectification) flame rod
- Detects ionisation in gaseous fuels flame zone
- Rod length: 305, 457, 610 mm and others on request
- Works with flame relay module MBCE-FR and controllers: MSeries II, Flame-MonitorTM E210, BurnerLogixTM
- Supply 280-305VAC from Fireye controller
- Operating temperature -40oC to 816oC, rod 1350oC
- Mounting 1/2" NPT
- BurnerPROTM is a compact, microprocessor-based, primary flame safeguard control system
- Provides the proper burner sequencing, ignition and flame monitoring for on-off, multistage, or modulating burners used in commercial heating and process equipment firing oil and gas
- The BurnerPROTM offers two built-in amplifiers, which allows for use in UV only, FR only, and UV+FR applications
- Works with UV non-self-checking scanners UV1A, UV90L and/or with flame rod 69ND1
- The FR amplifier circuitry is subjected to permanent self-checking - use in applications that require a burner cycle that runs for more than 24 hours. The UV amplifier has no self-checking - use in non-permanent run applications where burner recycle at least once every 24 hours
-
Seven SMART LED-s provides current operating status and lockout information in the event of a safety shutdown
- Non-volatile lockout capability
- Remote and local Reset
- Real-time internal diagnostics for added safety integrity
- Proof of fuel valve closure and air-flow proving
- A run/check feature allows the operator to stop the program sequence in different positions (Purge, Ignition, PTFI and MTFI) for system troubleshooting
- FFRT 1 second
- A complete BurnerPROTM system includes BP110/230 control, flame scanner (or flame rod) and wiring base
- Supply: BP230 - 230VAC or BP110 - 110VAC
- Surface-mounted in wiring base
- CE marked
BurnerPROTM control and wiring base
- Utilizes an UV lamp
- Version UV90L allows for front and lateral (90°) mounting
- Non self-checking
- Ambient temperature range: -40°C do 94°C
- Spectrum: 190-270 nm
- Works with: MBCE-UV, Burner PRO, NXF4000 Nexus, MSeries II, Flame-MonitorTM E210, NEXUS, BurnerLogixTM
- Supply 560 VAC only from controls as above
- Mounting thread 1/2“ NPT
- Available in version with ATEX Exd IIC T6 housing
UV90L
- Microprocessor-based burner controller and integrated boiler control
- Modular construction
- Automatic sequencing of the boiler system start and stop
- Full modulation control of fuel and air through the firing rate motor
- Multiple lead/lag operation of two or more boilers
- Works with scanners UV1A, 48PT2 flame rod 69ND1 and self-checking scanner 45UV5-1007
-
Keypad display system module in either VFD or LCD version, display 2-line x 16 characters featuring all info display mode, program and review of the system setpoints and operating parameters
- Remote display available
- The smart LED's on the front cover provides operating status and lockout information
- Non-volatile memory allows the control to remember its history and present position
- Solid-state sensors to monitor steam pressure and water stack and outdoor with selectable thresholds for limits and interlocks
- MODBUS communication via RS 485 multi-drop
- Supply 230VAC
- Surface-mounted on wiring base
- CE marked - certificate not actual
NOTE: The product is available as a spare part only. Contact IP&S companyfor the selection of a replacement controller
- IR photoresistor
- Non self-checking
- Reacts on flame flicker in range 12-25 Hz
- Temperature limits: -40°C do 60°C
- Works with controls: Flame-MonitorTM E210, NEXUS, BurnerLogixTM
- Supply 7 VDC from controls as above
- Available in explosion-proof housing ATEX Exd IIC T6
- Modular flame safeguard control with a changeable programmer and amplifier modules
- Provides the proper burner sequencing, ignition and flame monitoring
-
Uses UV1A, 48PT2 scanners, 45UV5-1007 self-checking scanner or flame rod 69ND1
-
Two-line 16 character display and keypad allows access to current and historical burner information
- Programmable E-300 Expansion Module provides interlock monitoring and first out announciation
- Remote reset and remote display E-510 capability
- MODBUS communication via RS 485
- Temperature rating -20 to 60°C
- Power input 230 VAC
- Surface-mounted on wiring base
- CE approved
NOTE: The product has been withdrawn from production. Contact IP&S companyfor the selection of a replacement control
- UV Geiger Muller lamp
- Optical range 190 – 270 nm – solar blind
- For clean gaseous and oil fuels
- Limited discrimination capabilities - for single burner applications
- Self-checking with electromagnetic shutter allows continuous operation
- Used with Fireye controls Flame-MonitorTM E210, BurnerLogixTM, D-Series
- Powered by control
- Wide temperature range -40 to +93°C
- Available explosion-proof housing ATEX Ex d IIC T6
- Approvals: FM, CSA, UL, CE
NOTE: The product is available as a spare part only. Contact IP&S company for the selection of a replacement integrated flame scanner
- A compact, modular burner management control for intermittent operation
- Plug-in amplifier and programmer modules are changeable
- Control provides automatic ignition and continuous flame monitoring for gas and oil burners
- Works with UV1A6 scanner or flame rod 69ND1
- LED's indicate the operating status of the control
- Remote reset capability
- Option: can work as a flame relay for igniters (intermittent operation)
- Temperature limits -40 to 60oC
- Power supply 230VAC
- Wall-mounted on wiring base
- CE approved - certificate not actual
NOTE: The product is available as a spare part only. Contact IP&S company for the selection of a replacement control or integrated flame scanner
- Flame relay module for ionization rod 69ND1 - MBCE-110/230FR - with self-checking
- Flame relay module for UV scanners UV1A and UV90L - MBCE-110/230UV
- Outputs: flame relay and analog 4-20mA
- Relay status ON/OFF and diagnostics LED's
- Safety time FFRT 1 or 3 sec
- Operating temperature -40oC to 65oC
- Supply 230VAC
- Panel surface or DIN rail mounting
- CE marked
MBCE-110/230UV