- Analog flame amplifier
- Monitor up to 2 flame scanners
- The 5166 has a high discrimination amplifier module (low sensitivity) and the 5168 has a high sensitivity (low discrimination) module
- Flame Failure Response Time: selectable 1 to 3 seconds
- Two independent gain settings
- 0-3 VDC flame signal strength test jacks
- Optional marginal alarm
- 10 LED flame strength signal indicator in option
- Surface mount on wiring base
- Analog output 0-20mA in option
- Supply voltage 120VAC/220VAC
- CE approved with appropriate scanners
NOTE: The product has been withdrawn from production. Contact IP&S company for the selection of a replacement integrated flame scanner