- UV Geiger Muller lamp
- Optical range 190 – 270 nm – solar blind
- For clean gaseous and oil fuels
- Limited discrimination capabilities - for single burner applications
- Self-checking with electromagnetic shutter allows continuous operation
- Used with Fireye controls Flame-MonitorTM E210, BurnerLogixTM, D-Series
- Powered by control
- Wide temperature range -40 to +93°C
- Available explosion-proof housing ATEX Ex d IIC T6
- Approvals: FM, CSA, UL, CE
NOTE: The product is available as a spare part only. Contact IP&S company for the selection of a replacement integrated flame scanner